Inductive Voltage Transformers
(Outdoor)

  • In Compliance with IEC / ANSI / IS Standards
  • Burden Up to 1200VA
  • Secondary Windings Up to 4
  • Frequency 50/60 Hz
  • Voltage Factor Up to 1.8 Continuous
  • Polymer / Porcelain Insulator
  • Service Temperature -50°C to +50°C
  • High Altitude
  • 0.5g Seismic Acceleration

Inductive Voltage Transformers (Outdoor)

Description / kV ClassUnit11kV22kV33kV66kV110kV132kV150kV
Applicable StandardIEC / IEEE / ANSI / IS
ConstructionDead Tank
Highest System VoltagekV12243672.5123145170
One Min. PF VoltagekV285070140230275325
Lightning Impulse VoltagekVp75125170325550650750
Rated FrequencyHz50 /60
Ambient Temperature° C-50 to +50
Seismic Levelg0.3
Voltage Factor1.2 Cont. & 1.5-30 Sec.
Rated Secondary Voltage110, 110 / √3 , 115, 115 / √3, 120, 120 / √3
Creepage Distancemm3006009001815307536254250
Burden & Accuracy100VA/0.5200VA/0.5300VA/0.5
Accuracy Class0.2 / 0.5 / 1.0 / 3.0 / 3P / 6P
Max No. of WindingsNo.3334444
Oil Level IndicatorBellows Level Indicator at Top
Pressure Relief DeviceStainless Steel Bellows
Oil VolumeStainless Steel Bellows
Separate Secondary BoxYes (on request)
On Request0.5g, High Creepage, High Altitude, Composite Insulator, 1.8 Voltage Factor etc.